High-performance CPU function at 0.015 μs/word for basic commands, 0.05 μs for application commands.
Program capacity of 180K words, equipment information memory of 4 Mbytes
Standardly equipped with a myriad of communication functions
SFC programming is supported (compliant with IEC61131-3)
* SFC (Sequential Function Chart)

TOYOPUC-PC10G

1. Features of TOYOPUC-PC10G

TOYOPUC-PC10G is a compact programmable controller with a high-speed computing function (0.015 μs/command at minimum), large capacity equipment information memory (4 Mbyte for standard) and a multitude of communication functions.

  • High-performance CPU function

    Various sequence programs such as "Equipment control", "Equipment diagnosis" and "Information processing" can be executed by high-speed processing using basic commands and application commands that are 0.015 μs/word and 0.05 μs/word faster than PC3JG, respectively. With more than 700 kinds of application commands, signed operation and floating point arithmetic are possible.

  • Large capacity memory

    The large capacity equipment information memory (4 Mbyte) stores helpful information useful for adjustment of equipment or maintenance work, such as comments, project, SFC and I/O diagram.
    The basic area of each program and the memory capacity of common areas have been significantly expanded. Due to the expansion of the basic area, it is possible to store the history of up to 64 CPU alarms events. A large capacity expansion USB flash drive of 4 Mbyte can be used.

  • A myriad of communication functions

    Ports L1 and L2 are provided to select FL-net, Ethernet or FL remote M capable of 100 Mbps communication. Built-in Ethernet is capable of 32 ports opened simultaneously.
    Port L3 is provided to select communication with CMP link (computer link), PC link, or SN-I/F (safety PLC TOYOPUC-PCS).
    By using USB2.0 in connection with PCwin, reading and writing of the program have been achieved at a higher speed than conventionally possible.

  • SFC programming is supported (compliant with IEC61131-3)

    Conventional LD (ladder) programming does not present straightforward “operation progress for individual equipment processes.” The SFC, however, presents these visually using flow charts. FBD can be used to standardize ladder circuits in units of functions, facilitating the reduction of drawings and reuse of equipment.
    LD (ladder) can also be exclusively used for programming.

    • ※SFC(Sequencial Function Chart)
    • ※FBD(Function Block Diagram)
    • ※IEC(International Electrotechnical Committee)

    (Note) Some function limitations apply to Ver. 3.00 or earlier.

2. Various new functions

TOYOPUC-PC10G Various new functions

3. General specifications

Item Specification
Power source POWER1: AC85〜264V 47〜66 Hz
POWER2: DC18〜32V
Consumption power POWER1: 38W or less (80VA or less)
POWER2: 40VA or less
Anbient temperature 0〜55°C
Relative humidity 30〜85%RH (But no condensation allowed.)
Atmosphere No corrosive gas allowed.
Vibration
resistance
Frequency Acceleration Amplitude Sweep cycles
10〜57Hz —— 0.15mm 10 cycles
(1 octave/min)
57〜150Hz 9.8m/s2 ——
Shock resistance (147 m/s2 3-directions each 3 shocks)
Dielectric
strength
AC1500V 1 minute (between AC external terminal and earth)
AC1000V 1 minute (between DC external terminal and earth)
Insulation
resistance
DC500V 10MΩ or more (between AC external terminal and earth)
DC100V 10MΩ or more (between DC external terminal and earth)
Instantaneous
power failure
POWER1: Allowable time: 0.5 cycle or less Period: 1s or more
POWER2: Allowable time: 10ms or less Period: 1s or more
Overseas standard North America CSA/NRTL acquired, Europe corresponds to CE mark RoHS
  • Note) The above is the specification common to each module.

4. Electromagnetic compatibility (EMC)

Item Standard Specification
Static electricity IEC61000-4-2 Gaseous discharge ±8kv
Contact discharge ±6kv
Burst test
(First transient test)
IEC61000-4-4 Signal line ±1kv
DC power line ±1kv
Function ground line ±1kv
Surge IEC61000-4-5 To ground ±1kv
Conducted interference of radio frequency electromagnetic field IEC61000-4-6 Frequency range 0.15-80 MHz
Voltage level 10 V (rms, non-modulated)
Modulation method 80% AM, modulated (1 kHz)
Radiated, radio frequency
Electromagnetic field immunity
IEC61000-4-3 Frequency range 80-1000 MHz
Voltage level 10 V (rms, non-modulated)
Modulation method 80% AM, modulated (1 kHz)

5. Control specifications

Model PC10G PC3JG-P
Program method Stored program method Event monitor function by parameter setting
Program control method Cyclic operation method
Constant period interruption function
Cyclic operation method
Programming language SFC, LD, FBD
Input/output control method Image registration method
Basic command processing speed Contact…0.015 μs or more/command Contact…0.08 μs or more/command
Application command processing speed 0.05-few μs/command 0.6-several tens of μs/command
Basic command 19 commands + 1 command (inversion output for screen buttons) 19 commands
Timer/counter command 21 commands + 1 ms timer, 1 s timer 21 kinds
Application command With more than 700 commands, signed operation and floating point arithmetic are possible 450 commands or more
Program capacity 180K words (60K words × 3)
(Can be selected from 60K words/60K words/60K words, 120K words/60K words and 180K words)
180K words (60K words × 3)
+ 60K words (FB library) + 60K words (FB library)
+ Standard library 32K words + Standard library 32K words
+ User library 32K words + User library 32K words
Memory element CMOS-RAM, E2PROM*2
Battery Rechargeable (lithium secondary battery: 5 years life)
No. of external I/O 2048 points
Internal I/O N.A. I/O 64 points
No. of internal outputs 86,016 points (4,096 points × 3 + 8,192 points + 65,536 points) 79,872 points (2,048 points × 3 + 8,192 points + 65,536 points)
No. of keep relays 6,400 points (768 points × 3 + 4,096 points)
Timer function 0.1-6553.5 sec./0.01-655.35 sec.
0.001-65.535 sec./1-65,535 sec. 9,728 points in total
0.1-6553.5 sec./0.01-655.35 sec. 3.584 points in total
Counter function 1-65535 (2,560 points × 3 + 2,048 points) 1-65535 (512 points × 3 + 2,048 points))
Link relay points 38,912 points (10,240 points × 3 + 8,192 points) 14,336 points (2,048 points × 3 + 8,192 points)
Rising and falling detection 11,776 points (2,560 points × 3 + 4,096 points) 5,632 points (512 points × 3 + 4,096 points)
Data register 164K words/16 bits (12K words × 3 + 128K words)
Extension buffer register 256K words/16 bits
164K words/16 bits (12K words × 3 + 128K words)
Extension buffer register 256K words/16 bits
Link register 6K words/16 bits (2K words × 3)
Equipment information memory 4 Mbyte 640 Kbyte
Special module installation amount Communication (link) module: Max. 24 modules Communication (link) module: Max. 15 modules
Memory consumption does not limit the number of modules Memory consumption: 60 Kbyte or less
Built-in communication function L1 port: FL-net/Ethernet/FL remote master L1 port: DLNK-M2
L2 port: FL-net/Ethernet/FL remote masterタ L2 port: SN-I/F, PC/CMP link
L3 port: SN-I/F, PC/CMP link -