TOYOPUC-PC3JT
1. Features of TOYOPUC-PC3JT
-
■ Slim and space-saving
The size is very compact, 55.2 mm in depth and 200 × 110 mm in footprint in the case of the basic configuration where the PC3JT-CPU, DLNK, I/O cover and base 2 are mounted. Its compact size allows it to be mounted on the operation panel, contributing to space-saving of the overall system.
-
■ Built-in communication ports
PC3JT-CPU has one built-in operation panel communication port and one built-in PC/CMP link as standard features. One additional port (DeviceNet master DLNK or As-i master As-i M) is available as an option.
-
■ A diversity of expansion modules
A wide variety of expansion modules are available to choose from.
2. General specifications of TOYOPUC-PC3JT
| Item | Specification | |||
|---|---|---|---|---|
| Power source | POWER1: AC85〜264V 47〜66 Hz POWER2: DC18〜32V POWER2H:DC18~32V |
|||
| Consumption power | POWER1: 38W or less (80VA or less) POWER2: 40VA or less POWER2H:50VA or less |
|||
| Anbient temperature | 0〜55°C | |||
| Relative humidity | 30〜85%RH (But no condensation allowed.) | |||
| Atmosphere | No corrosive gas allowed. | |||
| Vibration resistance |
Frequency | Acceleration | Amplitude | Sweep cycles |
| 10〜57Hz | —— | 0.15mm | 10 cycles (1 octave/min) |
|
| 57〜150Hz | 9.8m/s2 | —— | ||
| Shock resistance | (147 m/s2 3-directions each 3 shocks) | |||
| Dielectric strength |
AC1500V 1 minute (between AC external terminal and earth) AC1000V 1 minute (between DC external terminal and earth) |
|||
| Insulation resistance |
DC500V 10MΩ or more (between AC external terminal and earth) DC100V 10MΩ or more (between DC external terminal and earth) |
|||
| Instantaneous power failure |
POWER1: Allowable time: 0.5 cycle or less Period: 1s or more POWER2: Allowable time: 10ms or less Period: 1s or more |
|||
| Overseas standard | North America CSA/NRTL acquired, Europe corresponds to CE mark | |||
- Note) The above is the specification common to each module.
3. Control specifications of TOYOPUC-PC3JT
| Model | PC3JT | |
|---|---|---|
| Programming method | Stored program method | |
| Program control method | Cyclic operation method | |
| Input/output control method | Image registration method | |
| Basic instruction processing speed | Contact…0.08μs〜 /instruction | |
| Application instruction processing speed | 0.6μs〜few 10μs/instruction | |
| Basic instruction | 19 instructions | |
| Timer counter instruction | 21 instructions | |
| Application instruction | 450 instructions or more | |
| Program capacity |
16K words × 3 + Standard library 32K words + User library 32K words |
|
| Memory element | CMOS-RAM, Flash EPROM | |
| Battery | Rechargeable (Lithium secondary battery: battery longevity 5 years) | |
| No. of external I/O | 1024 points (Increase is possible by DeviceNet※ and remote I/O | |
| No. of internal output | 14,336 points (2,048 points × 3 + 8,192 points) | |
| No. of keep relay | 6,400 points (768 points × 3 + 4,096 points) | |
| Timer function Counter function |
0.1〜6553.5 sec / 0.01〜655.35 sec total 3,584 points 1〜65,535 (512 points × 3 + 2,048 points) |
|
| No. of link relay | 14,336 points (2,048 points × 3 + 8,192 points) | |
| Detection of start-up and start-down | 5,632 points (512 points × 3 + 4,096 points) | |
| Data register | 12K words / 16 bit (4K words × 3 + 32K words) | |
| Link register | 6K words / 16 bit (2K words × 3) | |
| Equipment data memory | 448Kbyte Program comment |
|
| Special module installation amount |
Communication (link) module: Max 15 sheets Consumption memory: 60Kbyte or less |
|
| Visualization function |
S F C | × |
| F B | × | |
| Library function | F B | × |
| Standard | × | |
| User | × | |
| Event monitor function (possible to monitor at the cycle) | × | |
| Compulsion ON/OFF function | × | |
| Scan unit trace function | × | |
| Maintenance support |
Equipment diagnosis function | × |
| Network diagnosis function | × | |
| I/O diagram display | × | |
| I/O recorder | × | |
| Test mode | × | |
| Programmer I/F | RS-422 38.4kbps | |
| Built-in communication function |
L1: PC / CMP L2: PC / CMP (except PC3JT) |
|
- *1 The range where special instruction is necessary for writing in.
- *2 PC10P can be equipped with the special module through the use of BUS-EXP (EXPANDED BUS) or Plus BUS-EX.
- *DeviceNet is the registered trademark of Open DeviceNet Vendor Association Inc.