Product information
TOYOPUC series
TOYOPUC PC3JL-CPU
A library function, PC / CMP-LINK:2 port standard, and 7 segment display machine are added for the function/form of PC3J-CPU as it is.
Furthermore, it contributes to lead time shortening of the work from circuitry to preservation.
1. The feature
-
1.TOYOPUC PC3J-CPU and Equivalent Function
Three independent program execution, Loading of an equipment information memory, high-speed processing, A flexible user memory
-
2.Library function
The load reduction of the sequence design and the number of sheets of the circuit drawing can be reduced by the library function. (Applicable only the PC3J mode.)
-
3.Event Monitor Ability
ON/OFF of an alarm coil is detected by the sampling function,and an alarm code is extracted corresponding to it.
A detailed,alarm display is supported by combining this function with the operation board. (Applicable only the PC3J mode.) -
4.Communication-2-Port-Build as Standard.
Two ports of PC /CMP links are built in as standard. A space-saving is realized.
-
5.The state display by 7 segment display machine
7 segment display machine is built in. The RUN/ERR/ALM state of CPU can check at a glance.
2. General specification
Items | Specification | ||||
---|---|---|---|---|---|
Power supply | AC85-264V 47 - 66 Hz (in the case of POWER1) DC 18-32V (in the case of POWER2) | ||||
Power consumption | Less than [ 38W ] (80 or less VA) (in the case of POWER1) 40 or less VA (in the case of POWER2) | ||||
Ambient temperature | 0-55℃ | ||||
Relative humidity | 30 - 85%RH (But no condensation allowed.) | ||||
Atmosphere | No corrosive gas allowed. | ||||
Vibration resistance | Conforming to JIS C0911. | Frequency | Acceleration | Amplitude | Sweep cycles |
10~57Hz | - | 0.15mm | 10 cycles (1 octave /minute) |
||
57~150Hz | 9.8m/s2 | - | |||
Shock resistance | Conforming to JIS C0912.(147m/s2 3 directions, 3 shocks in each direction) | ||||
Noise resistance nature | 1000V It is based on a P.P (1 microsecond of noise width) noise simulator. | ||||
Insulation resistance | For [ AC1500V ] 1 minute (during an AC external terminal-ground) For [ AC1000V ] 1 minute (during a DC external terminal-ground) 5V and OV It removes between terminals | ||||
Instant electric power failure | The instantaneous blackout permission time 0.5 or less cycles 1s or more (in the case of POWER1) of the instantaneous blackout intervals the instantaneous blackout permission time 10 or less ms 1s or more (in the case of POWER2) of the instantaneous blackout intervals | ||||
Consumption current | 390mA(Typ.) | ||||
Outside size | 35(W)×130(H)×110(D)mm | ||||
Mass | 0.22kg |
3. Performance specification
Items | The PC3J mode (initial cofiguration) | PC2 compatible mode | ||
---|---|---|---|---|
Total | Detail | |||
Program system | Stored program method | |||
Program control method | Cyclic operation method (subroutine function) Max. 3 programs | Cyclic operation method(subroutine function) | ||
Command kind | Basic Command: 19 sort, Timer counter command:21 sort, application command: 450 or more sorts | |||
Basic command processing speed | 0.08 to 0.28 us/command (Contact), 0.12 to 0.48us /command (Output) | |||
Application command processing speed | 0.60us (min.)/word | |||
Program capacity | Sequence | 48KW *1 | 16KW×3 | 32KW |
User library | 32KW(256)*2 | |||
I/O mark | 1024 points | 1024 points | ||
Internal relay | 14336 points *1 | 2048×3+8192 points | 2048 points | |
Keeping relay | 6400 points *1 | 768×3+4098 points | 768 points | |
Timer counter | 3584 points *1 | 512×3+2048 points | 512 points | |
Link relay | 14336 points *1 | 2048×3+8192 points | 2048 points | |
Data register | 12KW *1 | 4KW×3 | 12KW | |
Link register | 6KW *1 | 2KW×3 | 2KW | |
Built-in communication port | 2 link standard equipment - Link 1 :PC / CMP-LINK (built-in standard link) *3 *4 - Link 2 :PC / CMP-LINK (built-in option link) |
|||
The number of the maximum link mounting | 15 | 8 | ||
Equipment information memory | 448KB | 448KB *5 |
- *1:Change by selection of allotment of a user memory.
- *2:Only the PC3J mode corresponds.
- *3:In use, 4 line type communication is possible only for a port 1.
- *4:In an initial setup (he has no link parameter), operate as a computer link of standard specification.
- *5:It is necessary to use Hellowin.